Display LEDs + Backlit digital display
Voltage detection
Voltage 1.0 V to 299.0 VAC/DC
300 V to 1,000 VAC / 1,400 VDC
Frequency DC, 162/3 to 800 Hz
Impedance > 500 kΩ
Max. peak current 3.5 mA RMS
Polarity indication Yes
Redundant hazardous
voltage indication
The ELV (Extra Low Voltage) LED indicates a voltage
higher than the SELV (Safety Extra-Low Voltage) and
its flashing speed is proportional to the voltage
Stray voltage detection Yes (by low-impedance load switching)
RCD tripping Yes (by low-impedance load switching)
(30 mA approx. at 230 V)
Phase/Neutral
identification
Above 50 V (45 – 65 Hz)
Above 150 V (162/3 – 45 Hz)
Continuity & Resistance
Buzzer trigger threshold 100 Ω typical (150 Ω max.)
Extended continuity test
(Resistance) 0.5 Ω to 2.999 kΩ
Test current / Open-circuit
voltage ≤ 1 mA / ≤ 3.3 V
Phase rotation 2-wire method with microprocessor
Ph/Ph voltage 50 V ≤ U ≤ 1,000 Vac (45 – 400 Hz)
Buzzer Intermittent beep for voltage detection
Continuous beep for continuity
Standards and electrical
safety
IEC 61243-3:2009, EN 61243-3:2010, IEC 61010
1000 V CAT IV
Enclosure protection IP65
Climatic conditions -15 °C to +45 °C (Class N)
Battery life > 2,500 x10 s measurements
Dimensions / weight 228 x 60 x 39 mm (without test probe)
350 g approx.
-
Description
- |
-
Add Tags
- |
Tail sed sausage magna quis commodo snasae. Aliquip strip steak esse ex in ham hock fugiat in. Labore velit pork belly eiusmod ut shank doner capicola consectetur landjaeger fugiat excepteur short loin. Pork belly laboris mollit in leberkas qui. Pariatur snasae aliqua pork chop venison veniam. Venison sed cow short loin bresaola shoulder cupidatat capicola drumstick dolore magna shankle.
AVAILABILITY: In stock
The C.A 6418 earth/ground clamp, delivered in its carrying case, can be used for quick testing of earth loops, whatever their type. Its clamping capacity allows measurements on 30 x 40mm and 20 x 55mm rectangular bars and cables 32mm in diameter.
The C.A 6418 clamp simultaneously displays the earth-loop resistance and the leakage current.
Download Sales Brochure
AVAILABILITY: In stock
Voltage
Measurement range / resolution 1-700V / 1V
Accuracy / input impedance ±1.2% reading ± 1pt in AC+DC ; ±1% reading ± 1 ct in DC / 25 MΩ
Operating frequency DC; 30-440 Hz
Insulation
Test voltage 250-500-1000 V
Range at maximum test voltage 11 GΩ
Measurement range 250 V : 50 kΩ – 4,2 GΩ / 500 V : 100 kΩ – 4.2 GΩ / 1,000 V : 200 kΩ – 11 GΩ
AVAILABILITY: In stock
AVAILABILITY: In stock
Discover the CA 6418
oblong-headed earth
clamp
AVAILABILITY: In stock
Reference P01127012 P01127014
Voltage (UHE)
Range – 0.1-600V
Resolution – 0.1V
Accuracy – ± ( 1% reading + 1 ct)
2P resistance
Range 0.05-99.99 Ω / 80.0-999.9 Ω / 0.800-9.999 kΩ / 8.00-50.00 kΩ
Resolution 0.01 Ω / 1 Ω / 10 Ω / 100 Ω
Accuracy ± ( 2% reading + 10 ct) / ± ( 2% reading + 2 cts) / ± ( 2% reading + 1 ct) / ± ( 2% reading + 1 ct)
Cable compensation – up to 5 Ω
3P earth/ground resistance
Range 0.5 Ω – 2.000 kΩ 0.5 Ω – 50.00 kΩ
Resolution 0.01 Ω / 0.1 Ω / 1 Ω 0.01 Ω / 0.1 Ω / 1 Ω/ 10 Ω
Accuracy ±(1% reading + 10 cts) / ±(1% reading + 2 cts) / ±(1% reading + 1 ct)
Measurement frequency 128 Hz or 256 Hz
Open-circuit voltage ± 10 V peak
AVAILABILITY: In stock
Bandwidth 20 and 40 MHZ
Channels (number / type) 2 isolated
IEC61010 safety 1 000V CAT II – 600V CAT III
Analogue display or equivalent No
One-shot digital sampling rate 50 MS/s
Repetitive mode 2 GS/s
Vertical resolution 9 bits
Transient detection (Glitch) > 20ns
Scaling / physical unit •/•
PC communication / Ethernet USB •
Mains power supply / Battery •/•
AVAILABILITY: In stock
Locate hidden circuits!
Comprising a transmitter and a receiver, the LOCAT-N provides digital, visual and audio indication of the presence of cables or ducts so that you can follow them intuitively.
AVAILABILITY: In stock
The CA 6011 continuity tester has been specially designed for periodic testing of the protective earth conductors of electrical equipment, appliances and installations, linked in particular to the standards and regulations: IEC/EN 60364, NF C 15-100, VDE 100, etc.
The CA 6011 continuity tester has been specially designed for periodic testing of the protective earth conductors of electrical equipment, appliances and installations, linked in particular to the standards and regulations: IEC/EN 60364, NF C 15-100, VDE 100, etc.
These systematic, repetitive tests represent more than 80% of testing operations. Particular care must therefore be taken to prevent them from becoming tiresome.